Experimental testing of an oil-flooded hermetic scroll compressor |
| |
Authors: | Ian H Bell Eckhard A Groll James E Braun W Travis Horton |
| |
Affiliation: | 1. University of Liège, Department of Aerospace and Mechanical Engineering, Liège, Belgium;2. Purdue University, Department of Mechanical Engineering, 140 S. Martin Jischke Drive, West Lafayette, IN 47906, USA |
| |
Abstract: | In this work, a residential air conditioning compressor designed for vapor injection has been modified in order to inject large quantities of oil into the working chamber in order to approach an isothermal compression process. The compressor was tested with oil injection mass flow fractions of up to 45%. At an evaporating temperature of ?10 °C and condensing temperature of 30 °C, the overall isentropic efficiency was up to 70% at the highest oil injection rate. Overall, over the testing envelope investigated, there are no significantly negative effects experienced for the compressor and the compressor isentropic efficiency and refrigerant mass flow rate improve monotonically as the oil injection rate is increased. |
| |
Keywords: | |
本文献已被 ScienceDirect 等数据库收录! |
|