LCL滤波并网逆变器的进网电流相位矫正技术
引用本文:阚加荣,谢少军,姚志垒,薛迎成,吴冬春,李小凡.LCL滤波并网逆变器的进网电流相位矫正技术[J].电力系统自动化,2012,36(14):166-171.
作者姓名:阚加荣  谢少军  姚志垒  薛迎成  吴冬春  李小凡
作者单位:1. 盐城工学院电气工程学院,江苏省盐城市,224051
2. 南京航空航天大学自动化学院,江苏省南京市,210016
摘    要:文中分析了LCL滤波并网逆变器系统的稳定性。该并网逆变器采用逆变器侧电感电流作为反馈量,并采用电网电压前馈控制策略,由劳斯判据得到该系统恒稳定的结论。由闭环系统的传递函数确定了电压前馈系数的大小,并根据闭环系统的根轨迹设计了电流环的控制参数。分析了该闭环系统并网功率因数小于1的原因,为克服这一缺点,提出了进网电流相位矫正技术。该技术根据进网电流与电网电压之间的相位差调节电流环基准值的频率,最终使进网电流与电网电压同相位,并网功率因数等于1。进网电流相位矫正技术不会影响原有系统的稳定性。仿真结果验证了该策略的有效性。

关 键 词:LCL滤波器  并网逆变器  电流控制  功率因数  相位矫正
收稿时间:4/6/2011 2:00:40 PM
修稿时间:2012/6/11 0:00:00

A Phase Correction Technique for Grid Side Current of Grid-connected Inverter with LCL Filter
KAN Jiarong,XIE Shaojun,YAO Zhilei,XUE Yingcheng,WU Dongchun,LI Xiaofan.A Phase Correction Technique for Grid Side Current of Grid-connected Inverter with LCL Filter[J].Automation of Electric Power Systems,2012,36(14):166-171.
Authors:KAN Jiarong  XIE Shaojun  YAO Zhilei  XUE Yingcheng  WU Dongchun  LI Xiaofan
Affiliation:1(1.School of Electrical Engineering,Yancheng Institute of Technology,Yancheng 224051,China; 2.College of Automation Engineering,Nanjing University of Aeronautics and Astronautics,Nanjing 210016,China)
Abstract:According to the Routh criteria,a grid-connected inverter with a LCL filter is stable when the output current of the inverter is used as a feedback variable.The feed-forward coefficient of the grid voltage is obtained from the transfer function of the closed-loop system.The control parameters of the current-loop are designed according to the root locus.The power factor of the grid-connected inverter is not unity.To overcome this shortcoming,this paper proposes a phase correction technique for the grid side current of the inverter.The technique adjusts the frequency of reference current according to the phase separation between the grid voltage and the grid current.The proposed technique improves the power factor to unity.In addition,the technique hardly affects the stability of the closed-loop system.The simulation results verify that the performance of the proposed technique is excellent.
Keywords:LCL filters  grid-connected inverters  current control  power factor  phase correction