Purification of turbine condensate in the lumped desalinization units of the Mosénergo TÉTs-22 Heat and Electric Power Plant |
| |
Authors: | I A Malakhov É G Amosova P I Dolgopolov A P Dolgopolov L S Klimonova |
| |
Affiliation: | (1) JSC “énergoékoservis”, Moscow, Russia;(2) State Scientific Center of the Russian Federation JSC “NII VODGEO”, Moscow, Russia;(3) TéTs-22 of the JSC “Mosénergo”, Moscow, Russia |
| |
Abstract: | Purification of turbine condensate by mechanical and ion exchange resin (ionite) filters in lumped desalinization units is
examined. Loading mechanical filters with styrene copolymer and divinyl benzene ensures efficient removal of petroleum products
and iron, but does not fulfil the task of removing polar organic compounds. The ionite part of a lumped desalinization unit
ensures removal of easily electrolyzed compounds and silicic acid but is ineffective with regard to capture of organic contamination
and iron, which indicates significant contamination of the load in the combination filter by organic compounds. “Cold” (standard)
and “hot” regeneration of the anionite load are undertaken. Greater extraction of organic substances is observed with “hot”
regeneration.
Translated from élektricheskie stantsii, No. 5, May 2008, pp. 17–22. |
| |
Keywords: | turbine condensate power production unit neutral-oxygen regime lumped desalinization unit water-chemical regime filters filter load cationite anionite regeneration permanganate oxidizability iron compound specific electrical conductivity silicic acid organic substances |
本文献已被 SpringerLink 等数据库收录! |