基于Dd匹配变和SVG的牵引变电所群贯通供电系统负序治理方案及控制策略
引用本文:张宇,王辉,李群湛,解绍锋,张恒.基于Dd匹配变和SVG的牵引变电所群贯通供电系统负序治理方案及控制策略[J].高电压技术,2021,47(1):150-158.
作者姓名:张宇  王辉  李群湛  解绍锋  张恒
作者单位:西南交通大学电气工程学院,成都610031;西南交通大学电气工程学院,成都610031;西南交通大学电气工程学院,成都610031;西南交通大学电气工程学院,成都610031;西南交通大学电气工程学院,成都610031
基金项目:国家自然科学基金(51877182);四川省科技计划(2018GZ0044,2017CC0072);包神铁路集团课题资助(2018H010286)。
摘    要:牵引变电所群贯通供电方案是解决长大坡道、外部电源短路容量小且接口少的电气化铁路供电问题的有效技术手段之一。针对牵引变电所群贯通供电系统负序治理问题,提出了一种基于Dd匹配变和静止无功发生器(static var generator,SVG)的负序治理方案及控制策略。介绍了牵引变电所群贯通供电系统的结构,分析了其各端口电气量及关系,提出了适用不同牵引负荷功率因数的两种负序治理模式,并推导了负序治理数学模型。考虑电网三相电压不平衡度允许值,分析了不同工况下Dd匹配变次边各端口SVG投入容量,提出了补偿模式间切换策略。根据负序治理方案确定系统负序电流检测方法,提出了一种SVG双闭环控制策略。最后搭建了仿真模型,仿真结果表明方案的有效性和控制策略的准确性。

关 键 词:牵引变电所群贯通供电系统  负序治理  SVG  控制策略  负序电流检测

Negative Sequence Treatment and Control Strategy for the Co-phase Interconnected Power Supply System of Traction Substation Group Based on Dd Transformer and SVG
ZHANG Yu,WANG Hui,LI Qunzhan,XIE Shaofeng,ZHANG Heng.Negative Sequence Treatment and Control Strategy for the Co-phase Interconnected Power Supply System of Traction Substation Group Based on Dd Transformer and SVG[J].High Voltage Engineering,2021,47(1):150-158.
Authors:ZHANG Yu  WANG Hui  LI Qunzhan  XIE Shaofeng  ZHANG Heng
Affiliation:(School of Electrical Engineering,Southwest Jiaotong University,Chengdu 610031,China)
Abstract:The co-phase interconnected power supply system of traction substation group is a feasible technical solution to electrified railway power supply problem of long and steep slope, external power supply with poor short circuit capacity and lack of interface. Aiming at the problem of negative sequence current, a treatment scheme and its control strategy based on Dd transformer and SVG were proposed. The structure of co-phase interconnected power supply system of traction substation group was introduced, and the relationship of electrical quantity of its each port was analyzed. Then, two modes of negative sequence treatment were proposed, which were separately compatible to different traction load power factor. Meanwhile, a mathematical model was derived. The limit of three-phase unbalance was taken into consideration,and the reactive power capacity resolved by each SVG on secondary ports of the Dd transformer was analyzed when they were working under different conditions. Based on research above, a switching strategy between different modes was put forward. According to the scheme, the negative sequence current detecting methodology was determined and an SVG control strategy of double closed loop was proposed. Finally, the simulation model was built. Simulation results verify the effectiveness of the scheme and the accuracy of the control strategy.
Keywords:co-phase interconnected power supply system of traction substation group  negative sequence treatment  SVG  control strategy  negative sequence current detection