首页 | 本学科首页   官方微博 | 高级检索  
     


Faulty feeder identification in high impedance grounded network using charge-voltage relationship
Authors:T. Henriksen
Affiliation:SINTEF Energy Research, P.O.Box 4761 Sluppen, NO 7465 Trondheim, Norway
Abstract:The zero sequence impedance of a healthy feeder seen from the feeding bus bar in a network that is isolated or grounded by arc suppression coils is approximately equivalent to a capacitance. The instantaneous value of the integral of current (i.e. the charge) is then close to a linear function of the zero sequence voltage. One proposal in the literature is to identify the faulty feeder during a single phase to ground fault by the shape of the charge-voltage curves. A simple numerical criterion for identifying the faulty feeder has been established in this paper and it has successfully been applied to measurements obtained by a field test. The test did not include the most difficult identification conditions and those conditions have been analyzed by a computational model. The identification must be based on transients only when the network is overcompensated but the duration of the transients is sufficient for a reliable identification.
Keywords:Single phase to ground fault   Faulty feeder identification   Charge-voltage relation   Simple numerical criterion
本文献已被 ScienceDirect 等数据库收录!