首页 | 本学科首页   官方微博 | 高级检索  
     


Performance of distance relay mho elements on MOV-protectedseries-compensated transmission lines
Authors:Marttila  RJ
Affiliation:Ontario Hydro Res., Toronto, Ont.;
Abstract:It is shown that the applicability of memory-polarized distance relay mho elements to the protection of MOV (metal oxide varistor) protected series-compensated lines is dependent on the system configuration, line loading, the location of the potential source, and the magnitude of memory polarization. For a configuration with compensation at one end of a line, the results indicate certain advantages in using the potential from the line side of the capacitor, and the use of a relatively large magnitude of memory polarization. The presence of a conducting MOV enhances the performance of the mho element both in terms of security on reverse faults and dependability on forward faults. The results obtained pertain to the proposed application in the Ontario Hydro system of a relatively large amount of compensation at one terminal in each circuit of a double-circuit line
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号