整流装置跳闸原因及整改
引用本文:巢蒸. 整流装置跳闸原因及整改[J]. 氯碱工业, 2009, 45(3): 6-10
作者姓名:巢蒸
作者单位:中国石化集团资产经营管理有限公司巴陵石化分公司,湖南,岳阳,414014
摘    要:从离子膜法烧碱整流装置的保护原理出发,通过对某工厂在2005年整流装置跳闸原因的统计和技术分析,发现电网波动和雷击是整流装置跳闸的两个重要原因,并提出了采取修改整定值、增加防晃电交流接触器以及在低压交流侧增加三级防雷措施的整改对策。整改后,整流装置跳闸次数明显减少。

关 键 词:离子膜法烧碱  整流装置  跳闸  电网波动  雷击

Reasons of the rectifer tripping and the rectification and reform
CAO Zheng. Reasons of the rectifer tripping and the rectification and reform[J]. Chlor-Alkali Industry, 2009, 45(3): 6-10
Authors:CAO Zheng
Affiliation:Baling Branch Company of Assets Management Co.;Ltd.;SINOPEC;Yueyang 414014
Abstract:It is found that two main reasons of making the rectification devices trigger trip are electric net waving and thunderbolt strucking.Based on the protection principle of rectification devices for ion-exchange membrane caustic soda production devices by the statistics and technology analysis of rectification devices tripping reasons of the plant in the year of 2005,and the measures of rectification and reform are proposed,such as revising the rectification value,increasing alternating current contactors with...
Keywords:ion-exchange membrane caustic soda  rectification devices  electric net wave  tripping operation  thunderbolt strucking  