Analysis of hyperbolic cooling towers with local imperfections
Authors:KJ Han  GS Tong
Affiliation:

Department of Civil Engineering, University of Houston, Houston, TX 77004, USA

Shanghai Institute of Applied Mathematics und Mechanics, 149 Yan Chang Road, Shanghai, 200072, China

Abstract:Two methods to analyse hyperbolic cooling towers with local imperfections are presented. One method relies on the finite element technique. For this a specialized finite-element program, which can model any arbitrary imperfections while retaining the advantage offered by the basically axisymmetric nature of the shell, was developed. The other method is an approximate procedure, which may be implemented with a purely axisymmetric analysis capability. The two methods are compared through numerical studies. A cooling tower shell with a bulge-type imperfection is examined under dead load and wind load conditions. It is concluded that the finite-element model presented is effective for the analysis of such shells, while the equivalent-load method may be adequate for some cases. Also, it is shown that both meridional and circumferential stress resultants may be radically influenced by a small bulge imperfection.
Keywords:cooling tower  bulge imperfection  finite element  equivalent load