Cellulose-pad water cooling system with cold storage
Affiliation:1. Department of Energy Conversion and Storage, Technical University of Denmark, Frederiksborgvej 399, Roskilde DK-4000, Denmark;2. Technical Institute of Physics and Chemistry, Chinese Academy of Sciences, Beijing 100190, China;3. University of Science and Technology Beijing, Beijing 100083, China;4. Institute of Physics, Chinese Academy of Sciences, Beijing 100190, China
Abstract:The present study develops a cooling system using water as the working medium which is cooled at night by cellulose-pad cooling tower (CWCT) and stored for cooling application at daytime. That is, it utilizes the natural energy drawn from diurnal ambient air temperature difference. A cooling system was built and tested. It is found that the coefficient of performance of CWCT for heat dissipation of water at night, COPnt, is between 3.8 and 11 and varies linearly with the evaporation temperature glide DG (difference between cold water temperature in the storage tank and wet-bulb temperature of ambient air). The COP for room cooling at daytime run with air cooler in a room, COPday, is between 8.8 and 12.6. For day cycle operation, the measured overall cooling COPo is 5.1. COPo is expected to reach 9.4 at room temperature 45 °C.
Keywords:
本文献已被 ScienceDirect 等数据库收录!