Power quality assessment in 3-Ф grid connected PV system with single and dual stage circuits |
| |
Affiliation: | 1. Shanxi Electric Power Research Institute, No.6 Qingnian Road, Taiyuan 030001, China;2. NARI Group Corporation, No.19 Chengxin Avenue, Nanjing 211106, China |
| |
Abstract: | This paper addresses the assessment of power quality (PQ) in 3-Ф grid connected photovoltaic (PV) system that consists of single and dual stage power extraction circuits. The single stage circuit comprises of Z-source inverter (ZSI) controlled by space vector pulse width modulation (SVPWM), while dual stage is traditional boost based voltage source inverter controlled by sinusoidal pulse width modulation. The PQ of signals in both the circuits is analyzed during transient variations like solar intensity and load conditions, with/without use of hybrid filter. The simulation and experimental results suggest an improved smooth sinusoidal waveform available at PCC in case of ZSI based circuit using hybrid filter, if power quality improvement is of prime importance with both linear and nonlinear load connected in the system. |
| |
Keywords: | Power quality PV system SVPWM Z-source inverter Hybrid filter |
本文献已被 ScienceDirect 等数据库收录! |
|