首页 | 本学科首页   官方微博 | 高级检索  
     

基于无源控制策略的MMC-DVR控制系统
引用本文:周雅婷,程启明,江畅,谢怡群,傅文倩,叶培乐. 基于无源控制策略的MMC-DVR控制系统[J]. 太阳能学报, 2022, 43(10): 275-280. DOI: 10.19912/j.0254-0096.tynxb.2021-0293
作者姓名:周雅婷  程启明  江畅  谢怡群  傅文倩  叶培乐
作者单位:1. 上海电力大学自动化工程学院,上海 200090;2. 上海市电站自动化技术重点实验室,上海 200090
基金项目:国家自然科学基金(61905139); 上海市电站自动化技术重点实验室资助项目(13DZ2273800)
摘    要:为了提高高压电网电压质量补偿效果,提出基于模块化多电平换流器(MMC)的动态电压调节器(DVR)系统的无源非线性控制方法。首先,介绍MMC-DVR的框图以及工作原理,根据基尔霍夫电压电流定律,分别构建abc静止与两相dq旋转坐标系下的数学模型;接着提出无源控制方法来解决问题;最终,在Matlab/Simulink软件实验平台上构建MMC-DVR系统,构建仿真验证无源非线性控制的可行性和优越性。与传统PID相比,无源策略能使系统迅速稳定,提高抗扰能力,采取阻尼注入,能快速、有效地对电压降落/升高和谐波进行补偿,并且无源非线性控制器控制规律简单,所需控制器数量少,可避免PI控制参数选择困难及繁复的缺点。

关 键 词:风电场  动态电压调节器  无源控制  模块化多电平转换器  动态电压  
收稿时间:2021-03-18

MMC-DVR CONTROL SYSTEM BASED ON PASSIVITY CONTROL STRATEGY
Zhou Yating,Cheng Qiming,Jiang Chang,Xie Yiqun,Fu Wenqian,Ye Peile. MMC-DVR CONTROL SYSTEM BASED ON PASSIVITY CONTROL STRATEGY[J]. Acta Energiae Solaris Sinica, 2022, 43(10): 275-280. DOI: 10.19912/j.0254-0096.tynxb.2021-0293
Authors:Zhou Yating  Cheng Qiming  Jiang Chang  Xie Yiqun  Fu Wenqian  Ye Peile
Affiliation:1. College of Automation Engineering, Shanghai University of Electric Power, Shanghai 200090, China;2. Shanghai Key Laboratory Power Station Automation Technology Laboratory, Shanghai 200090, China
Abstract:MMC-DVR combined with dynamic voltage regulator(DVR) and modular multilevel converter (MMC) can be used to solve the problem of sag/swell compensation for medium and high voltages. Since MMC-DVR is a non-linear system, the compensation effect of linear control methods such as PID commonly used in DVR systems is not satisfactory. To this end, this paper proposes a passive nonlinear control method for the MMC-DVR system, which can be deeply integrated in the wind farm grid-connected system, and can solve the negative problems such as power quality degradation. First, the circuit topology and working principle of MMC-DVR are introduced, and the mathematical model under the static and rotating coordinate system is established. Then, the passive control method is proposed to solve the problem. Finally, the MMC-DVR control system is built on Matlab/Simulink software experimental platform, and the experimental results verify the feasibility and superiority of the passive nonlinear control strategy proposed in this paper.
Keywords:wind farm  dynamic voltage restorer (DVR)  passivity-based control (PBC)  modular multilevel converter  dynamic voltage  
点击此处可从《太阳能学报》浏览原始摘要信息
点击此处可从《太阳能学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏