首页 | 本学科首页   官方微博 | 高级检索  
     


Effect of magnetic field on the performance of new refrigerant mixtures
Authors:Samuel M Sami  Shawn Aucoin
Affiliation:Mechanical Engineering, School of Engineering, University of Moncton, Moncton, NB, E1A 3E9, Canada

Research Assistant.

Abstract:Performance test results of new alternative refrigerant mixtures such as R-410A, R-507, R-407C, and R-404A under various conditions of magnetic field are discussed, analysed and presented. The test results were obtained using an air-source heat pump set-up with enhanced surface tubing under various magnetic field conditions. Performance tests were conducted according to the ARI/ASHRAE Standards. The test results demonstrated that as magnetic field force increases, compressor head pressure and discharge temperature slightly increase as well as less liquid refrigerant is boiling in the compressor shell. This has a positive effect in protecting the compressor. The effect of magnetic field on mixture behaviour varies from one mixture to another depending upon the mixture's composition and its boiling point. Furthermore, the use of magnetic field appears to have a positive influence on the system COP as well as thermal capacities of condenser and evaporator. Copyright © 2002 John Wiley & Sons, Ltd.
Keywords:new refrigerant mixtures  magnetic–caloric effect  ARI/ASHRAE standards
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号