首页 | 本学科首页   官方微博 | 高级检索  
     


Equivalent circuit model for the insulated core transformer
Affiliation:1. China Electric Power Research Institute, Nanjing 210003,China;2. State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan 430074, China
Abstract:The design of the insulated core transformer(ICT)needs to consider the flux leakage effects.An equivalent linear circuit model is proposed based on the principle of duality.It is composed by two types of leakage inductances:conventional leakage between windings and special leakage introduced mainly by the insulation gaps.The values of leakage inductances depend on the dimensions of the core,gaps,or windings and the property of magnetic materials.The circuit allows for quantitatively evaluating influences of ICT internal parameters on its output properties.The winding self- and mutual inductance matrix is mathematically converted to derive the inductance formula.As an example,the leakage parameters of a sixstage two-dimensional(2D) ICT are calculated and analyzed.
Keywords:High-voltage power supply  Insulated core transformer  Leakage inductance  Equivalent circuit
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏