首页 | 本学科首页   官方微博 | 高级检索  
     


AC side harmonic and phenomena accompanying DC-injection of utility-interactive PV system
Authors:Kholid Akhmad   Hiroaki Okamoto   Akio Kitamura   Hiromu Matsuda   Fumio Yamamoto  Yoshihiro Hamakawa
Abstract:The experiments investigated phenomena related to direct contact between the DC output of a PV array and the AC power from the utility grid. The results show that the DC power flows through the distribution transformers (DC-injection) saturating their magnetic circuits. The saturation of magnetic circuits makes peak currents, incorporating a large portion of even harmonics, flow through the high-voltage side of the distribution transformer, adding the level of harmonic distortion of its exciting current. With the increase of injecting DC-current to the utility grid, peak currents at the primary side of distribution transformer increases the most, and even among the same effective (rms) values, the increase of primary side current is larger than that of the secondary side current.
Keywords:DC-injection   Utility-interactive PV system