500 kV CVT计量误差现场测试分析 |
| |
引用本文: | 耿建坡,王永辉,魏雯雯,史轮,孙冲,岳国义,陶鹏.500 kV CVT计量误差现场测试分析[J].河北电力技术,2012(5):3-4. |
| |
作者姓名: | 耿建坡 王永辉 魏雯雯 史轮 孙冲 岳国义 陶鹏 |
| |
作者单位: | [1]河北省电力公司电力科学研究院,石家庄050021 [2]北京市电力公司,北京100031 |
| |
摘 要: | 针对一起电能计量装置数据异常现象,对CVT进行现场误差测试,发现0.2级CVT电压计量误差达0.30%~0.45%,通过原理分析认为CVT高压电容部分元件击穿是造成误差大的原因,并提出在系统运行方式许可时,电能计量装置中电压互感器选用电磁式电压互感器的建议。
|
关 键 词: | CVT 电能计量 误差 电容击穿 |
500 kV CVT Measurement Error Site Test Analysis |
| |
Abstract: | In view of unnormal data of electric energy measurement,makes the CVT site error test, finds the error of 0.2 level CVT electric energy measurement is 0. 30% 0.45% ,through principle analysis, and considers that CVT high voltage capacitor breakdown is leading the large error, and advances the suggestion that voltage interconvert should choose electromagnetic voltage interconvert during permissive system operation mode. |
| |
Keywords: | CVT electric energy measurement error capacitor breakdown |
本文献已被 CNKI 维普 等数据库收录! |
|