An analytic method for measuring accurate fundamental frequencycomponents
Authors:Soon-Ryul Nam Sang-Hee Kang Jong-Keun Park
Affiliation:Sch. of Electr. Eng., Seoul Nat. Univ.;
Abstract:This paper proposes an analytic method for measuring the accurate fundamental frequency component of a fault current signal distorted with a DC-offset, a characteristic frequency component, and harmonics. The proposed algorithm is composed of four stages: sine filter, linear filter, Prony's method, and measurement. The sine filter and the linear filter eliminate harmonics and the fundamental frequency component, respectively. Then Prony's method is used to estimate the parameters of the DC-offset and the characteristic frequency component. Finally, the fundamental frequency component is measured by compensating the sine-filtered signal with the estimated parameters. The performance evaluation of the proposed method is presented for a-phase to ground faults on a 345 kV 200 km overhead transmission line. The electromagnetic transient program (EMTP) is used to generate fault current signals under different fault locations and fault inception angles. It is shown that the analytic method accurately measures the fundamental frequency component regardless of the characteristic frequency component as well as the DC-offset