光伏电站中光伏组件串联数的优化设计
引用本文:杨旭,易坤,左超. 光伏电站中光伏组件串联数的优化设计[J]. 太阳能, 2021, 0(3): 68-74
作者姓名:杨旭  易坤  左超
作者单位:中国电建集团贵州工程有限公司
摘    要:目前在光伏电站设计中,光伏组件串联数的计算广泛使用GB 50797-2012或IEC 62548-2016中的计算方式,假定在极端环境低温的情况下对光伏组串的开路电压、最大功率点电压等进行计算,进而确定光伏组件成串数量,即光伏组件串联数.但随着对光伏电站度电成本的要求日益严苛,上述对于计算光伏电站的光伏组件串联数的要求...

关 键 词:光伏电站  度电成本  光伏组件串联数  开路电压  优化设计

OPTIMIZATION DESIGN OF SERIES NUMBER OF PV MODULES IN PV POWER STATION
Yang Xu,Yi Kun,Zuo Chao. OPTIMIZATION DESIGN OF SERIES NUMBER OF PV MODULES IN PV POWER STATION[J]. Solar Energy, 2021, 0(3): 68-74
Authors:Yang Xu  Yi Kun  Zuo Chao
Affiliation:(Power China Guizhou Engineering Co.,Ltd.,Guiyang 550003,China)
Abstract:At present,the calculation method of series number of PV modules in GB 50797-2012 or IEC 62548-2016 is widely used in the design of PV power station,which assumes the calculation of open circuit voltage and maximum power point voltage of PV module string under extreme ambient low temperature conditions,and then determines the series number of PV modules.With the requirements for LCOE have become increasingly stringent,and the requirements of the national standard have been conservative in the series number of PV modules.The latest edition of IEC 62738-2018 proposes to use the annual average minimum ambient temperature for series number of PV modules calculations,and no longer requires extreme ambient low temperatures for calculations.If the data is sufficient,it is allowed to calculate the minimum ambient temperature limited to the sunshine time.On this premise,based on the recent experience in the calculation of the series number of PV modules of PV power station in international super large projects,we have realized the prediction of the relationship between the minimum ambient temperature and solar irradiance on the basis of a large number of meteorological data,and on this basis,the open circuit voltage and maximum power point voltage of PV modules string are calculated,the method to determine the series number of PV modules.Taking a project in the Middle East as an example,the serise number of PV modules calculated will be 2~4 more than the number calculated by GB 50797-2012 or IEC 62548-2016.It can significantly save the investment in PV power stations and reduce the LCOE.
Keywords:PV power station  LCOE  series number of PV modules  open circuit voltage  optimization design