首页 | 本学科首页   官方微博 | 高级检索  
     


Computational and experimental test of self starting regimes for the in-house needs of the PGU-450 steam-gas unit at the Kaliningrad TÉTs-2 Heating and Power Plant during supply disruptions
Authors:S N Sakharov  V A Kuz’michev
Affiliation:(1) EéS Engineering Center — branch of ORGRéS, Moscow, Russia
Abstract:The major stages of a computational test of the self starting regimes for the in-house needs of unit No. 1 of the 450 MW steam-gas unit at the Kaliningrad TéTs-2 Heating and Electric Power Plant during supply disruptions are described. The results of an experimental test of five regimes are described and compared with the computational data. The results are analyzed. Recommendations are made for changes in the automatic reserve switching algorithms for the 6-kV sections, which, when realized, will ensure easier self startup for the mechanisms providing for in-house needs during supply disruptions. __________ Translated from élektricheskie Stantsii, No. 4, April 2008, pp. 46–55.
Keywords:Steam-gas unit  in-house needs  self-startup regime  supply disruption
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号