首页 | 本学科首页   官方微博 | 高级检索  
     

中俄背靠背换流站直流系统与静止无功补偿器的协调运行
引用本文:殷威扬,刘宝宏,马世英,赵良.中俄背靠背换流站直流系统与静止无功补偿器的协调运行[J].电网技术,2007,31(12):57-62.
作者姓名:殷威扬  刘宝宏  马世英  赵良
作者单位:1. 国网直流工程建设有限公司,北京市,东城区,100005
2. 中国电力科学研究院,北京市,海淀区,100085
摘    要:为解决中俄联网背靠背换流站中国侧交流系统较弱的问题,在换流站中国侧安装了配合直流系统运行及提高交流系统暂态稳定性的静止无功补偿器(static var compensator,SVC)。从抑制换流母线暂态电压波动、提高交流滤波器/电容器分组容量及提高换流站中国侧交直流系统稳定性的角度考虑,通过仿真确定了换流站装设SVC的容量。同时结合SVC的特性及直流系统的性能要求,分析了直流系统和SVC在不同运行方式下的运行特性,提出了SVC的控制目标及SVC配合直流系统运行的协调控制原则。

关 键 词:中俄联网  背靠背换流站  静止无功补偿器  无功配置  协调运行  电压波动
文章编号:1000-3673(2007)12-0057-06
修稿时间:2007-01-08

Coordinated Operation of HVDC/SVC in China-Russia Back-to-Back Converter Station
YIN Wei-yang,LIU Bao-hong,MA Shi-ying,ZHAO Liang.Coordinated Operation of HVDC/SVC in China-Russia Back-to-Back Converter Station[J].Power System Technology,2007,31(12):57-62.
Authors:YIN Wei-yang  LIU Bao-hong  MA Shi-ying  ZHAO Liang
Affiliation:1. State Grid DC Project Construction Co., Ltd, Dongcheng District, Beijing 100005, China; 2. China Electric Power Research Institute, Haidian District, Beijing 100085, China
Abstract:The AC system at the China side of China-Russia back-to-back converter station located at China-Russia border is weak, to solve this problem a static var compensator (SVC) will be installed to match up with the operation of HVDC system and enhance transient stability of AC system. By means of simulation the capacity of the SVC is decided while following factors, such as restraining transient voltage fluctuation of converter bus, increasing the capacity of sectionalized banks of AC filter/capacitor and improving the stability of both AC and HVDC systems at China side, are taken into account. According to characteristics of SVC and performance verification of HVDC system, the operation characteristics of HVDC and SVC under different operating conditions are analyzed; on this basis the control objectives of SVC and the coordinated control principle by which SVC matches up with the operation of HVDC are proposed.
Keywords:interconnection of power grids of China and Russia  back-to-back converter station  SVC  reactive compensation  coordinated operation  voltage fluctuation
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《电网技术》浏览原始摘要信息
点击此处可从《电网技术》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号