首页 | 本学科首页   官方微博 | 高级检索  
     


Flow boiling of ammonia in a plain and a low finned horizontal tubeEbullition en éncoulement d'ammoniac dans un tube lisse ou un tube ailetté
Authors:S Kabelac  H -J de Buhr
Abstract:Experimental data of the local heat transfer coeffcient of flow boiling ammonia in dependence of vapor fraction, mass flux and local heat flux is presented. Two horizontal test sections of 450 mm length and an inner diameter of 10 mm have been used, one being a plain tube, one being a spirally low finned tube. A constant wall temperature boundary has been aimed for the test section by heating with a fluid condensing on the tube outside. Local heat transfer coeffcients and pressure drops have been measured in the range −40 < Tsat < 4°C, 0 < x< 0.9, 50 < < 150 kg/m2 s and 2 < ΔTw < 15 K with resulting heat fluxes of 17 < < 75 kW/m2. The vapor quality is denoted as x, is the mass flux and ΔTw the wall superheat. The measured data is carefully evaluated using a finite element model of the tube with regard to the circumferential heat flow distribution. The smooth tube results are compared with recently published data and the correlation from Zürcher (Zürcher, O., Thome, J.R., Favrat, D. Evaporation of ammonia in a smooth horizontal tube: heat transfer measurements and predictions. Journal of Heat Transfer, 1999;121:89–101), and with the correlations of Steiner (Steiner D. Strömungssieden gesättigter Flüssigkeiten. VDI-Wärmeatlas, vol. 8. VDI-Verlag, 1997) and Kattan (Kattan N, Thome JR, Favrat D. Flow boiling in horizontal tubes: part 3 — development of a new heat transfer model based on flow pattern. Transactions of the ASME, 1998;120). The results of the low finned tube are not matched by any known correlation.
Keywords:Heat transfer  Boiling  Ammonia  HFC  Heat transfer coefficient  MeasurementAuthor Keywords: Transfert de chaleur  Ebullition  Ammoniac  Tube  Coefficient de transfert de chaleur  Mesure
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号