首页 | 本学科首页   官方微博 | 高级检索  
     

气体绝缘金属封闭开关设备接地开关短路事故分析
引用本文:卢启付,李兴旺,程养春,谢志扬,金向朝. 气体绝缘金属封闭开关设备接地开关短路事故分析[J]. 广东电力, 2011, 24(11): 106-108
作者姓名:卢启付  李兴旺  程养春  谢志扬  金向朝
作者单位:1. 广东电网公司电力科学研究院,广东广州,510080
2. 华北电力大学新能源电力系统国家重点实验室,北京,102206
3. 广东电网公司佛山供电局,广东佛山,528000
基金项目:973项目资助(2009CB724508)
摘    要:以一起气体绝缘金属封闭开关设备(gas insulator switchgear,GIS)接地开关短路事故为例,分析事故发生的原因是隔离开关气室内金属异物在电场力和机械振动的作用下,引起盆式绝缘子沿面放电,导致绝缘破坏;在重合闸过程中,盆式绝缘子再次发生放电,电弧在气流的作用下,引起隔离开关静触头屏蔽罩与筒壁发生短路,...

关 键 词:气体绝缘金属封闭开关设备  隔离开关  短路事故  装配清洁度

Analysis on Short Circuit Accident of Earthing Switch of Gas Insulated Metal-enclosed Switchgear
LU Oi-fu , LI Xing-wang , CHENG Yang-chun , XIE Zhi-yang , JIN Xiang-chao. Analysis on Short Circuit Accident of Earthing Switch of Gas Insulated Metal-enclosed Switchgear[J]. Guangdong Electric Power, 2011, 24(11): 106-108
Authors:LU Oi-fu    LI Xing-wang    CHENG Yang-chun    XIE Zhi-yang    JIN Xiang-chao
Affiliation:1.Electric Power Research Institute of Guangdong Power Grid Corp.,Guangzhou,Guangdong 510080,China;2.State Key Laboratory of Power System with Renewable Energy Sources,North China Electric Power University,Beijing 102206,China;3.Foshan Power Supply Bureau of Guangdong Power Grid Corp.,Foshan,Guangdong 528000,China)
Abstract:The paper takes a short circuit accident of earthing switch of gas insulated metal-enclosed switchgear as an example to analyze that it is caused by discharge on the verge of cone type insulator resulting from metal objects in the chamber under the action of electric field force and mechanical vibration,which breaks the insulation.During the reclosing,the cone type discharges once more,which causes short circuit between shielded enclosure of fixed contact and tunnel wall under the action of airflow-affected electric arc,and shielded enclosure is consequently burnt out by heavy current.It is judged that inexact installation environment and impurity such as metal objects severely threaten safety of GIS.It also puts forward suggestions like strengthening control of GIS production and keeping the interior of GIS clean.In the meantime,importance of PD test should be attached to and GIS with PD signals should be examined in time to ensure safe and stable operation of grid.
Keywords:GIS  disconnecting switch  short circuit accident  installation cleanness