断路器防跳回路失灵案例分析及改进措施
引用本文:董超,胡楠楠. 断路器防跳回路失灵案例分析及改进措施[J]. 南方电网技术, 2012, 6(1): 91-93
作者姓名:董超  胡楠楠
作者单位:中国南方电网调峰调频发电公司惠州蓄能水电厂,广东 惠州516100;广东省电力工业职业技术学校,广州510520
摘    要:分析了一起500 kV断路器的防跳回路失效故障,指出故障是由远方控制程序导致,具体原因是断路器合闸脉冲时间设定不合理和继电保护动作未能闭锁断路器合闸命令。提出相应的改进措施,包括:将断路器的合闸脉冲时间由60 s改为0.5 s;在断路器内部故障与断路器合闸闭锁条件中加入断路器的保护动作信号。

关 键 词:防跳回路;控制程序;断路器;失灵

Analysis on a Case of Anti-Bouncing Circuit Malfunction of Circuit Breaker and Related Measures
DONG Chao and HU Nannan. Analysis on a Case of Anti-Bouncing Circuit Malfunction of Circuit Breaker and Related Measures[J]. Southern Power System Technology, 2012, 6(1): 91-93
Authors:DONG Chao and HU Nannan
Affiliation:Huizhou Pumped Storage Power Station of CSG Power Generation Company , Huizhou, Guangdong 516100, China;Guangdong Province Vocational and Technical School of Electric Power Industry, Guangzhou 510520, China
Abstract:A case of anti-bouncing circuit malfunction of circuit breaker is analyzed . And it's mainly caused by the remote control program. The concrete reason is the closing time is not suitable and the protection tripping signals don't block the closing order of the circuit breaker. Related measures have been suggested, including: reduce the closing time pulse from 0.5 s to 60 s, add protection tripping signals into the inner fault condition and closing blocking condition.
Keywords:anti-bouncing circuit   control program   circuit breaker   malfunction