Abstract: | This paper describes a control scheme of fault current limiter by series voltage injection. The current limiter proposed in this study is based on the use of a SMES‐based series‐connected voltage sag compensator, which has been previously studied by the authors, for controlling fault current caused by short circuit on the load side. An algorithm for fast discriminating between power system voltage sag and load‐side short circuit is proposed for the equipment to correctly function either for voltage sag compensation or for fault current limiting purpose. Furthermore, a new control strategy based on output voltage phase control of the series compensator is proposed for current limiting with good waveform characteristics and low active power absorption. Experimental results demonstrated the validity of the proposed strategy. © 2006 Wiley Periodicals, Inc. Electr Eng Jpn, 155(2): 64–72, 2006; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.20128 |