分流板结构对微通道平行流蒸发器性能的影响
引用本文:刘巍,朱春玲.分流板结构对微通道平行流蒸发器性能的影响[J].化工学报,2012,63(3):761-766.
作者姓名:刘巍  朱春玲
作者单位:南京航空航天大学人机与环境工程系
摘    要:试验研究了仅改变微通道平行流蒸发器内第一个分流板上的开孔数量和位置时,蒸发器的流动和换热性能的变化规律。结果表明:分流板的开孔数量和位置对蒸发器的流动和换热性能影响很大。合理布置分流板的结构,可以改善蒸发器内的流量分配,从而提高蒸发器的制冷能力,同时压降也会上升,且上升幅度大于制冷量的增加幅度。分流板上的总开孔面积一定时,开孔数量和位置的变化对蒸发器的内部阻力系数没有影响。分流板上的开孔数量太少及开孔位置偏离中心都不利于流量的均匀分配。分流相对均匀的第一个分流板的结构是:开孔数量是扁管数量的一半,开孔位置与相邻两扁管的投影等距。

关 键 词:微通道蒸发器  分流板  流量分配  对流换热  
收稿时间:2011-05-30
修稿时间:2011-08-26

Effects of deflector structure on performance of micro-channel evaporator with parallel flow
LIU Wei , ZHU Chunling.Effects of deflector structure on performance of micro-channel evaporator with parallel flow[J].Journal of Chemical Industry and Engineering(China),2012,63(3):761-766.
Authors:LIU Wei  ZHU Chunling
Affiliation:(Department of Man-Machine-Environment Engineering,Nanjing University of Aeronautics and Astronautics,Nanjing 210016,Jiangsu,China)
Abstract:Three different micro-channel evaporators with parallel flow were designed with the only difference in the structure of the first deflector,with the same open area but different number and location of holes.The performance of three evaporators was tested with refrigerant 134a under the same conditions.Flow and heat transfer characteristics in the evaporators were investigated with different number and location of holes in deflectors.The results show that the structure of deflector affects the flow and heat transfer performance of the evaporator remarkably.An appropriate structure of deflector can improve the uniformity of flow distribution,cooling capacity and pressure drop.The increase in pressure drop is faster than that of cooling capacity.With the same open area of holes in the deflector,their number and location in deflectors have no effect on the resistance coefficient of the evaporator.Insufficient holes in deflectors may generate the mal-distribution of refrigerant and deteriorate the heat transfer performance of the evaporator.When the holes in the deflector are not in the middle of two neighboring flat tubes,flow of the refrigerant is limited and the uniformity of flow distribution gets worse.The optimal structure of the first deflector is that the number of holes is half of that of the flat tubes,and the projection location of each hole has the same distance from two adjacent flat tubes.
Keywords:micro-channel evaporator  deflector  flow distribution  convective heat transfer
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《化工学报》浏览原始摘要信息
点击此处可从《化工学报》下载全文