35kV真空断路器开断并联电容器组过电压研究
引用本文:杨涛.35kV真空断路器开断并联电容器组过电压研究[J].贵州电力技术,2014(9):7-9.
作者姓名:杨涛
作者单位:贵州电力试验研究院,贵州贵阳550002
摘    要:当断路器发生单相重燃时,电容器组中性点会产生高频振荡,出现较大的过电压,这一过电压传递到电容器上,导致电容器对地也出现较高过电压,而电容器极间无过电压产生。当断路器发生两相重燃时,除了中性点和电容器对地出现过电压外,电容器极间也会出现过电压。由于并联电容器开断时间和重燃时间存在随机性,并不总是在最严重的时刻发生,因此实际的过电压较仿真结果要小。

关 键 词:真空断路器  并联电容器  重燃过电压  电磁暂态程序(EMTP)

Study on the overvoltage caused by 35 kV vacuum circuit breaker switching off shunt capacitors
YANG Tao.Study on the overvoltage caused by 35 kV vacuum circuit breaker switching off shunt capacitors[J].Guizhou Electric Power Technology,2014(9):7-9.
Authors:YANG Tao
Affiliation:YANG Tao(Guizhou Electric Power Testing & Research Institute, Guiyang 550002 Guizhou, China)
Abstract:Neutral point of capacitor bank would produce high-frequency oscillation and appear larger overvohage when the circuit breaker in single-phase rekindle. Overvoltage in capacitor to ground was too high, and the capacitor electrode did not produce overvoltage. The capacitor electrode would produce overvoltage when the circuit breaker in two-phase rekindle. The breaking time and rekindle time of the parallel capacitor were random, the realistic overvohage was smaller than simulation result.
Keywords:vacuum circuit breaker  shunt capacitors  restrike overvoltage  EMTP
本文献已被 维普 等数据库收录!