变电站10kV线路开关保护回路的探讨
引用本文:刘晗,苏小青,胡俊俊.变电站10kV线路开关保护回路的探讨[J].江西电力,2009,33(2):25-26.
作者姓名:刘晗  苏小青  胡俊俊
作者单位:九江供电公司,江西,九江,332000
摘    要:不少变电站进行10kV线路控制回路综合自动化改造成微机保护后,经常出现跳/合闸线圈烧毁情况,针对烧毁原因进行分析发现,通过是由于开关机构故障造成跳/合闸困难、保险容量选择不当、电压过高、控制回路一些接点不能延时返回致使长时间通电等造成烧毁线圈。对此,提出了解决的的办法和措施。

关 键 词:控制回路  保护  措施

10kV transmission lines switch protection loop of integrated substation
Liu Han,Shu Xiaoqin,Hu Junjun.10kV transmission lines switch protection loop of integrated substation[J].Jiangxi Electric Power,2009,33(2):25-26.
Authors:Liu Han  Shu Xiaoqin  Hu Junjun
Abstract:Coil burnout often happened after microcomputer protection implemented in 10 kV control circuit.Reasons of burnout were analyzed such as trip or closing difficulty caused by switch mechanism fault,improper insurance capacity and voltage overtension.Solutions were proposed:use high quality circuit breaker,maintenance,suitable insurance capacity and reform on loop voltage.
Keywords:control loop  protection  measure  