循环冷却水系统发生停泵水锤故障分析处理
引用本文:李颖昌.循环冷却水系统发生停泵水锤故障分析处理[J].黑龙江电力,2011,33(4):305-307.
作者姓名:李颖昌
作者单位:广东省粤泷发电有限责任公司,广东罗定,527217
摘    要:压力供水管路系统中,由于设计有驼峰且出水蓄能止回阀关闭过程过快,将导致正常停泵关阀时断流弥合水锤的产生.针对粤泷公司出现水锤故障,阐述了解决水锤问题的方法,即采取增设自动空气阀及调整阀门关闭时间.经实践验证,改造效果良好,循环冷却水系统运行稳定.

关 键 词:循环冷却水系统  水锤  蓄能液控止回阀

Fault analysis and treatment of water hammer recirculating cooling water system
LI Yingchang.Fault analysis and treatment of water hammer recirculating cooling water system[J].Heilongjiang Electric Power,2011,33(4):305-307.
Authors:LI Yingchang
Affiliation:LI Yingchang(Guangdong Yuelong Power Generation Company Limited,Luoding 527217,China)
Abstract:In pressure water supply pipeline,because of the designed hump and too rapid closing of hydraulic control check valve in the outlet,water hammer due to cavities collapsing is generated when the pump is closed.Aiming at the water hammer taking place in Yuelong Company,this paper expounds the solution of water hammer,which is to add automatic air valve and adjust the valve closing time.Practice proves that the transformed recirculating cooling water system works stably.
Keywords:recirculating cooling water system  water hammer  energy storage hydraulic control check valve  