Abstract: | In this paper we present a transient current analysis of induction generators used in a wind power system before and after three‐phase fault conditions. First, the basic equations of an induction generator connected to an infinite bus are developed and then transient current analysis formulas are derived for a three‐phase fault before and after fault clearance. We also determine the initial phase angle for the three‐phase fault or the restoration phase angle of the power supply voltages and the time at which the maximum or minimum transient currents flow in the system. © 2004 Wiley Periodicals, Inc. Electr Eng Jpn, 148(1): 38–45, 2004; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10319 |