首页 | 本学科首页   官方微博 | 高级检索  
     


Impacts of equipment off-design characteristics on the optimal design and operation of combined cooling,heating and power systems
Affiliation:1. Department of Chemical Engineering, McMaster University, 1280 Main St W, Hamilton, ON, L8S 4L7, Canada;2. Department of Materials Process Engineering, Nagoya University, Furo-cho 1, Chikusa, Nagoya 464-8603, Japan;3. School of Chemical and Biomolecular Engineering, Georgia Institute of Technology, 311 Ferst Drive NW, Atlanta, GA 30332-0100, USA
Abstract:Optimal design and operation of combined cooling, heating and power (CCHP) systems are complicated due to the fluctuating energy demands. Many mathematical models for the design and/or operation of CCHP systems have been developed. Most of them adopt a constant efficiency assumption, whilst others take equipment off-design characteristics into account. In this paper, we present two mathematical models for the optimal design and operation of CCHP systems with the target of minimising the total annual cost. One model is formulated using the constant efficiency assumption. In the other model, off-design characteristics of all equipments are considered. Comparative studies using different models were performed to examine the impacts of equipment off-design characteristics on the accuracy of the optimal design of CCHP systems. Results show that introduction of thermal storage facilities, connection to power grid and well designed operation strategies can diminish the negative impacts of adopting the constant efficiency assumption.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏