首页 | 本学科首页   官方微博 | 高级检索  
     

线缆混合输电线路行波故障定位系统的研发与应用
引用本文:张富春,高峰.线缆混合输电线路行波故障定位系统的研发与应用[J].南方电网技术,2012,6(2):112-115.
作者姓名:张富春  高峰
作者单位:1. 中国南方电网超高压输电公司广州局,广州510663
2. 武汉三相电力科技有限公司,武汉430074
摘    要:由于架空线和海底电缆的波阻抗不同,基于双端定位原理的行波故障定位装置在线-缆混合输电线路中无法发挥作用。根据海南联网工程的需要,开发了分布式行波故障定位系统。通过在架空线和海底电缆交界处安装行波故障定位监测终端,记录故障行波方向、GPS时间和行波在不同介质中的传播速度,从而实现故障的区间定位和精确定位。该系统应用于海南联网工程500 kV福港线,其运行情况显示系统工作是安全、可靠的。

关 键 词:架空线  海底电缆  故障定位
收稿时间:7/4/2011 12:00:00 AM

The Development and Apllication of Traveling Wave Fault Locating System for Transmission Line Consisting of Overhead Conductors and Submarine Cables
ZHANG Fuchun and GAO Feng.The Development and Apllication of Traveling Wave Fault Locating System for Transmission Line Consisting of Overhead Conductors and Submarine Cables[J].Southern Power System Technology,2012,6(2):112-115.
Authors:ZHANG Fuchun and GAO Feng
Affiliation:Guangzhou Bureau, CSG EHV Power Transmission Company, Guangzhou 510405, China;Wuhan Sunshine Power Science & Technology Co., Ltd., Wuhan 430074, China
Abstract:Due to the discrepancy of wave impedances between overhead lines and submarine cables, traveling wave fault location based on the dual side positioning principle can not adjust to the cable hybrid transmission lines. According to the needs of Hainan's networking project, the distributed traveling wave fault location system is developed. Through installing monitoring terminals of traveling wave fault location at the junction of overhead lines and submarine cables, traveling wave direction, GPS time, and wave propagation velocity in different media can be recorded, and thus achieving fault interval mapping and precise positioning. The system is applied to 500 kV Fushan - Gangcheng line, known as Hainan's networking project, whose operation verifies the system's safty and reliability.
Keywords:overhead lines  submarine cables  fault location