首页 | 本学科首页   官方微博 | 高级检索  
     


Application of Code Approach for Emergency Evacuation in a Rail Station
Authors:Kai Kang
Affiliation:(1) Jacobs, 260 Madison Avenue, 12th Floor, New York, NY 10016, USA
Abstract:This paper presents an emergency evacuation analysis during a mid-platform train fire in an underground rail station. A time-based evacuation scenario is developed taking into account the stairway inaccessibility due to smoke blockage. The calculation approach in NFPA 130 is then applied to a parametric study of this time-based scenario and its reliability is examined using a micro-simulation model. Both methods give consistent predictions of the exiting times. The results demonstrate that with the division of the station into two zones, the exiting time could not meet the code requirements, whereas it does meet the required exiting time without the division. Such division is due to smoke blockage and creates an uneven ratio of the occupant load to the available exiting capacity. This shows that appropriate consideration of the fire and smoke effects is important for station egress evaluation. Other issues such as the fire growth rate and the pre-evacuation time are also discussed.
Keywords:evacuation  rail station
本文献已被 SpringerLink 等数据库收录!