首页 | 本学科首页   官方微博 | 高级检索  
     


The performance of a transcritical CO2 cycle with an internal heat exchanger for hot water heating
Authors:Sung Goo Kim  Yoon Jo Kim  Gilbong Lee  Min Soo Kim  
Affiliation:aDA Network Business, Samsung Electronics Co. Ltd, Suwon 442-742, South Korea;bSchool of Mechanical and Aerospace Engineering, Seoul National University, Seoul 151-742, South Korea
Abstract:The main purpose of this study is to investigate the performance of a transcritical CO2 cycle with an internal heat exchanger for hot water heating. Performance test and simulation have been carried out for a transcritical CO2 cycle by varying secondary heat transfer fluid temperatures at evaporator and gas-cooler inlets as well as the discharge pressure. Variations of mass flow rate of refrigerant, compressor power, heating capacity, and co-efficient of performance (COP) with respect to the length of an internal heat exchanger are presented at various operating conditions. Good quantitative agreement between model predictions and experimental results has been found; most parameters have absolute average deviations of less than 4%. As the length of the internal heat exchanger increases, COP is enhanced but heating capacity tends to decrease due to the trade-offs between the effectiveness and pressure drop in the internal heat exchanger.
Keywords:Experiment  Transcritical cycle  CO2  Heat exchanger  Gas cooling  Heating  Water  Performance  COPMots clé  s: Expé  rimentation  Cycle transcritique  CO2  É  changeur de chaleur  Refroidissement de gaz  Chauffage  Eau  Performance  COP
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号