电流二次回路两点接地造成母差异常告警的处理与分析
引用本文:曹东,周程. 电流二次回路两点接地造成母差异常告警的处理与分析[J]. 冶金动力, 2014, 0(10): 12-13
作者姓名:曹东  周程
作者单位:国网安徽省电力公司马鞍山供电公司,安徽马鞍山243000
摘    要:母线保护是变电站继电保护系统中的一个重要的组成元件,但由于现场接线错误或由于电流回路的虚接地造成CT二次回路两点或多点接地的现象时有发生。通过一次异常事故处理,详细分析了两点接地的原理以及危害。并提出检查两点接地的方法。

关 键 词:母线保护  电流回路  两点接地  查找处理

Treatment and Analysis of Abnormal Alarm of Busbar Differential Caused by Two-point Grounding of CT Secondary Loop
CAO Dong,ZHOU Cheng. Treatment and Analysis of Abnormal Alarm of Busbar Differential Caused by Two-point Grounding of CT Secondary Loop[J]. Metallurgical Power, 2014, 0(10): 12-13
Authors:CAO Dong  ZHOU Cheng
Affiliation:(Maanshan Power Supply Company, Maanshan, Anhui 243000, China)
Abstract:Busbar protection is an important part in the relaying protection system of a transformer substation, but field wiring mistakes or false grounding of current circuits often lead to two-point or multi-point grounding of CT secondary loops. Through handling of an abnormal failure, the mechanism and harm of two-point grounding are analyzed in detail and method for checking two-point grounding is provided.
Keywords:busbar protection  current circuit  two-point grounding  search and treat-ment