Results of Complex Tests of the TGMP-314 Boiler of Cogeneration Plant-23 of the Mosénergo Company After Renovation |
| |
Authors: | Yu P Enyakin N A Zroichikov B N Glusker I V Galas Yu M Tsypkin V Z Zaretskii B P Enyakin B N Nosov V V Chuprov S N Anichkov V A Vereshchatin |
| |
Affiliation: | (1) All-Russia Thermal Engineering Institute (VTI), Russia.;(2) Mosénergo Cogeneration Plant-23, Russia.;(3) ORGRÉS, Russia.;(4) Russia. |
| |
Abstract: | Results of complex tests of the TGMP-314 boiler of thermal power plant-23 of the Mosénergo Company operating on natural gas and furnace oil after design improvement are presented. Toxic emissions of nitrogen oxides were diminished by the use of low-toxicity burners, supply of air to secondary blow nozzles, and introduction of recirculating gases into the burner channels. These measures lowered the emissions of NOx, benz(a)pyrene, and other harmful substances into the atmosphere below the standardized values. The boiler proved to operate reliably in the entire range of tested loads in the gas- and oil-fired modes with stage firing and recirculation of flue gases. The rated parameters of live steam and reheat steam were steadily maintained. |
| |
Keywords: | nitrogen oxides benz(a)pyrene natural gas oil fuel low-toxicity burners recirculation two-stage firing reliability of operation |
本文献已被 SpringerLink 等数据库收录! |