Logic unconstrained multi-zone evaporator and condenser models |
| |
Authors: | Liang-Liang Shao Chun-Lu Zhang |
| |
Affiliation: | aInstitute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200240, China;bChina R&D Center, Carrier Corporation, 3239 Shen Jiang Road, Shanghai 201206, China |
| |
Abstract: | The multi-zone model is widely used in evaporator and condenser modeling. The basic two-zone evaporator model and three-zone condenser model might reduce to one-zone or two-zone model depending on the operating conditions. In the traditional multi-zone models, logic constraints are invoked to separate the possible running modes and trigger mode changes from one to another, which will lead to the complicated logic in implementation. A logic unconstrained multi-zone model has been developed in this paper. In the new model, all the logic constraints are transformed into continuously differentiable equations. As a result, all the equations can be solved simultaneously without any logic constraints. Numerical examples show that the new logic unconstrained multi-zone models are in good agreement with the traditional ones. |
| |
Keywords: | Refrigeration Air conditioning Process Modelling Evaporator CondenserMots clé s: Froid Conditionnement d’ air Procé dé Modé lisation É vaporateur Condenseur |
本文献已被 ScienceDirect 等数据库收录! |
|