数据机房热区内气流组织的数值模拟及优化
引用本文:沈向阳,陈嘉澍,吕金虎,陆建峰,杨建平.数据机房热区内气流组织的数值模拟及优化[J].节能技术,2011,29(3):233-237,280.
作者姓名:沈向阳  陈嘉澍  吕金虎  陆建峰  杨建平
作者单位:1. 仲恺农业工程学院机电工程学院,广东,广州,510225;中山大学工学院,广东,广州,510006
2. 仲恺农业工程学院机电工程学院,广东,广州,510225
3. 中山大学工学院,广东,广州,510006
4. 华南理工大学传热强化与过程节能教育部重点实验室,广东,广州,510640
摘    要:建立数据机房热区内气流流动和传热的物理及数学模型,利用Fluent软件模拟其热区内气流的速度、温度和压力分布,模拟值和实测值相吻合。针对模拟数据机房热区内气流组织的缺点,从节能的角度提出改善方案,再通过Fluent软件模拟分析。研究结果表明:数据机房热区内最佳空调送风风速为3.6 m/s;SUN4900服务器的最佳放置方式是全交错放置且全交错距离为0.3 m。

关 键 词:数据机房  数值模拟  热区  气流组织

Numerical Simulation and Optimization of Air Distribution in a Data Center's Hot-zone
SHEN Xiang-yang,CHEN Jia-shu,LV Jin-hu,LU Jian-feng,YANG Jian-ping.Numerical Simulation and Optimization of Air Distribution in a Data Center's Hot-zone[J].Energy Conservation Technology,2011,29(3):233-237,280.
Authors:SHEN Xiang-yang  CHEN Jia-shu  LV Jin-hu  LU Jian-feng  YANG Jian-ping
Affiliation:SHEN Xiang-yang1,2,CHEN Jia-shu1,LV Jin-hu1,LU Jian-feng2,YANG Jian-ping3(1.College of Mechannical & Electrical Engineering,Zhongkai University of Agriculture and Engineering,Guangzhou 510225,China,2.School of Engineering,Sun Yat-sen University,Guangzhou 510006,3.Key Laboratory of Enhanced Heat Transfer and Energy Conservation of the Ministry of Education,South China University of Technology,Guangzhou 510640,China)
Abstract:The model of flow and heat transfer for data center' hot-zone has been set up.The velocity distribution,temperature distribution and pressure distribution of the data center's hot-zone are simulated by FLUENT simulation software.The simulated values fit well with the measured values.As for the defect of air distribution in hot-zone,an optimized project is given from the energy conversation perspective,which is simulated and analyzed by FLUENT simulation software.The results show that the best supply air vel...
Keywords:data center  numerical simulation  hot-zone  air distribution  