Practical Design Model for Calculating Bubble Diffuser Contactor Ozone Transfer Efficiency
Authors:Kerwin L. Rakness  Robert C. Renner  Bob A. Hegg  Archibald G. Hill
Abstract:Ozone transfer to water or wastewater is necessary before desirable, effective ozone reactions occur. Several factors affect ozone transfer efficiency, including water quality characteristics, contactor configuration, and applied ozone characteristics. The design model presented in this paper addresses all factors affecting ozone transfer. The model was used to compare measured transfer efficiency with predicted transfer efficiency at four full-scale wastewater ozone disinfection facilities. A relatively good prediction was obtained at each plant.

The paper presents an example calculation of ozone transfer efficiency. Also, the effect of changes to some of the factors affecting transfer efficiency is presented, such as changes in diffuser depth, plant elevation, ozone concentration, water quality (i.e., ozone demand), pH, detention time, temperature, and acombination of factors. The design model may be used to evaluate the effect of changes in plant design on transfer efficiency, but cannot provide an absolute value for transfer efficiency until difficult-to-measure parameters, such as bubble diameter, are known.

Keywords:Ozone  Transfer Efficiency, Contacting  Bubble Diffuser Contactors  Design Model for Calculating Ozone Transfer Efficiency  Wastewater Disinfection with Ozone