Volatile organic compounds from building products—Results from six round robin tests with emission test chambers conducted between 2008 and 2018
Authors:Olaf Wilke  Wolfgang Horn  Matthias Richter  Oliver Jann
Affiliation:Bundesanstalt für Materialforschung und -prüfung (BAM), Berlin, Germany
Abstract:Emission testing of volatile organic compounds (VOC) from materials and products is commonly based on emission test chamber measurements. To ensure the comparability of results from different testing laboratories, their measurement performance must be verified. For this purpose, Bundesanstalt für Materialforschung und -prüfung (BAM) organizes an international proficiency test (round robin test, RRT) every two years using well-characterized test materials (one sealant, one furniture board, and four times a lacquer) with defined VOC emissions. The materials fulfilled the requirements of homogeneity, reproducibility, and stability. Altogether, 36 VOCs were included of which 33 gave test chamber air concentrations between 13 and 83 µg/m3. This is the typical concentration range to be expected and to be quantified when performing chamber tests. Three compounds had higher concentrations between 326 and 1105 µg/m3. In this paper, the relative standard deviations (RSD) of BAM round robin tests since 2008 are compared and the improvement of the comparability of the emission chamber testing is shown by the decrease of the mean RSD down to 28% in 2018. In contrast, the first large European interlaboratory comparison in 1999 showed a mean RSD of 51%.
Keywords:construction product  emission test chamber  interlaboratory comparison  proficiency testing  round robin test  VOC emission
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号