首页 | 本学科首页   官方微博 | 高级检索  
     


Quantitative filter forensics: Size distribution and particulate matter concentrations in residential buildings
Authors:Alireza Mahdavi  Jeffrey A. Siegel
Affiliation:Department of Civil and Mineral Engineering, University of Toronto (UofT), Toronto, ON, Canada
Abstract:We applied filter forensics, the analysis of dust from the heating, ventilation, and air-conditioning (HVAC) filters, to measure particle size distribution in 21 residences in Toronto, Canada over a year. Four filters with different nominal efficiencies (Minimum Efficiency Reporting Value (MERV) 8–14 from ASHRAE Standard 52.2) were deployed in each residence each for three months, while the effective filtration volumes (the product of flow rate, runtime, and in-situ filter efficiency) were characterized over each filter lifetime. Using extraction and laser diffraction, we found that approximately 90% of the volumetric distributions were >10 µm and the volume median diameter (VMD) ranged from 23.4 to 75.1 µm. Using quantitative filter forensics (QFF), total suspended particle (TSP) concentrations ranged from 2.9 to 823.7 µg/m3 (median = 89.8 µg/m3) with a moderate correlation with the content of TSP on the filters (in terms of g) and with the TSP effective filtration volume (m3) indicating the importance of both filter forensics and HVAC metadata parameters to QFF concentration estimates. There was no strong correlation between PM10 or PM2.5 concentrations and hourly airborne particle number concentrations measured by low-cost sensors suggesting an evaluation of QFF is warranted, particularly for the exploration of smaller particles.
Keywords:dust  filtration  HVAC  laser diffraction particle sizer  volume median diameter
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号