The use of the ISO/TC92 test for ignitability assessment
Authors:XiFang Hu  Ferrers R. S. Clark
Affiliation:1. The Tianjin Fire Research Institute, Ministry of Public Security, Peoples' Republic of China;2. Fire Research Section, Institute for Research in Construction, National Research Council Canada, Ottawa, Canada, K1A OR6
Abstract:The ignitability of solids, including fire-retardant-containing polystyrene, is reported using results of a small-scale thermal radiation exposure test (a modified ISO ignitability test procedure). Additional information is provided from the results of exposure to convective heating and from oxygen index determinations. The use of a permanent sample mask and smaller samples than described in the ISO procedure proved convenient. The ISO procedure was found useful for determining the response of ignition time to changes in radiant flux. Good agreement was found with the analysis of Quintiere and Harkleroad for most samples but not with polystyrene, with and without halogen fire retardant. The increase in ignition resistance with fire retardant concentration suggested by the oxygen index is not always consistent with the ignition delay times under radiative or convective assault.