摘    要:针对变电站用VRLA蓄电池浅放电试验的蓄电池剩余电荷量预测、健康状态评价、终止放电条件等关键技术进行研究,形成的浅放电电池容量预测模型,并从浅放电的有效性和安全性出发,提出了终止放电的三个条件.文中利用二项式拟合预测模型,经迭代计算,预测蓄电池的容量.结果 证明,用该方法预测蓄电池容量的相对误差小于6%,实际放电时间误...

关 键 词:VRLA蓄电池  浅放电  容量预测  终止放电

Research on Key Technologies of Shallow Discharge Test of VRLA Battery in Substation
YANG Feng,ZHAO Dingfeng,LU Wenxu,TAN Zhiguang. Research on Key Technologies of Shallow Discharge Test of VRLA Battery in Substation[J]. Guangxi Electric Power, 2021, 44(1): 63-68,76
Authors:YANG Feng  ZHAO Dingfeng  LU Wenxu  TAN Zhiguang
Affiliation:(Yulin Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Guangxi Yulin 537000,China;Nanning Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Guangxi Nanning 530000,China;Guigang Power Supply Bureau of Guangxi Power Grid Co.,Ltd.,Guangxi Guigang 537100,China)
Abstract:Aimed at the shallow discharge test of VRLA battery in substation,key technologies are researched including the prediction of battery remaining power,the evaluation of health state,and the condition of discharge termination and so on.And a shallow discharge battery capacity prediction model is built.Based on the effectiveness and security of shallow discharge,three conditions for discharge termination are proposed.The binomial fitting prediction model is used in this paper to predict the battery capacity by iterative calculation.The result proves that the relative error of the battery capacity prediction is less than 6%by using the method,and the actual discharge time error is within 30 minutes,which is suitable for project application.