首页 | 本学科首页   官方微博 | 高级检索  
     

电流互感器油色谱单氢超标试验对比分析
引用本文:孙凌涛,刘建国,李旸.电流互感器油色谱单氢超标试验对比分析[J].广西电力,2021,44(1):50-55,86.
作者姓名:孙凌涛  刘建国  李旸
作者单位:内蒙古电力(集团)有限责任公司薛家湾供电局,内蒙古自治区 鄂尔多斯市 017100
基金项目:国家重点研发计划(电动汽车储能关键技术)(2017YFB0102304);内蒙古电力公司科技项目(延长电气设备试验周期新技术)(20161102);薛家湾供电局自主科技项目(电流互感器试验新技术的研究与应用)(510115190008)。
摘    要:为进一步明确电流互感器中超标氢气来源,针对某供电局220 kV光明变电站158明久Ⅱ回C相电流互感器油色谱氢气含量过万mL/L且无乙炔产生展开原因分析.首先通过油色谱与绕组介损试验并结合现场经验初步判断故障原因为绕组受潮且激励因素为油纸中局部放电.接着在得到油中微水及苯含量后通过计算分析及论证确定过量氢气主要来源于环己...

关 键 词:电流互感器  油色谱  氢气    环己烷

Comparison and Analysis of Tests for Exceeding Standard of Single Hydrogen in Oil Chromatography of Current Transformer
SUN Li.Comparison and Analysis of Tests for Exceeding Standard of Single Hydrogen in Oil Chromatography of Current Transformer[J].Guangxi Electric Power,2021,44(1):50-55,86.
Authors:SUN Li
Affiliation:(Xuejiawan Power Supply Bureau,Inner Mongolia Power(Group)Co.,Ltd.,Inner Mongolia Ordos 017100,China)
Abstract:To further clarify the source of excessive hydrogen in the current transformer,the cause why the oil chromatogram of the C-phase current transformer of No.158 MingjiuⅡline in 220 kV Guangming Substation of a Power Supply Bureau exceeded 10,000 mL/L without acetylene generation is analyzed.Firstly,through oil chromatography and winding dielectric loss tests and combined with field experience,it is preliminarily judged that the reason for the fault is that the winding is damp and the driving factor is partial discharge in the oil paper.Then,after obtaining the micro-water and benzene content in the oil,it is determined,through calculation analysis and demonstration,that the excessive hydrogen mainly comes from the dehydrogenation reaction of cyclohexane and the secondary source is the electrolysis of micro-water in the oil.Finally,it was determined by disassembly inspection that the cyclohexane originated from the adhesive in the paper.And the absorption of the infrared spectrum was observed in the infrared spectrum and partial discharge comparison test,so as to confirmed that the cyclohexane in the adhesive had a dehydrogenation reaction under the partial discharge environment,which was the main source of excessive hydrogen in the current transformer.Based on this,reasonable suggestions are proposed from the aspects of production,operation and maintenance.
Keywords:current transformer  oil chromatography  hydrogen  benzene  cyclohexane