首页 | 本学科首页   官方微博 | 高级检索  
     

小电流接地故障谐波分析及其对谐波选线的影响
引用本文:薛永端,高旭,苏永智,李长安. 小电流接地故障谐波分析及其对谐波选线的影响[J]. 电力系统自动化, 2011, 35(6): 60-64
作者姓名:薛永端  高旭  苏永智  李长安
作者单位:1. 中国石油大学(华东)信息与控制工程学院,山东省东营市,257061
2. 华北电网有限公司,北京市,100053
3. 山东电力集团公司,山东省济南市,250001
4. 山东山工机械有限公司,山东省青州市,262500
摘    要:针对小电流接地系统单相接地故障的谐波选线原理,分析了电源侧、负荷侧和故障点自身的谐波源及其产生的故障谐波电流特征,在分别分析其独立作用对谐波选线影响的基础上,综合分析了多谐波源共同作用时对谐波选线的影响.研究表明:电源侧和负荷侧谐波源起主导作用,其主要通过故障点故障前谐波电压体现;故障点谐波源产生的谐波电流小、作用可忽略;各谐波源的大小、相位和故障点相对谐波源的位置是影响谐波选线的主要因素.仿真验证了上述观点.

关 键 词:小电流接地系统  小电流接地故障  谐波分析  故障选线  谐波选线
收稿时间:2010-05-12
修稿时间:2011-03-07

Analysis of Harmonic in Non-solidly Earthed Network and Its Influences on Harmonic-based Earth Fault Protection
XUE Yongduan,GAO Xu,SU Yongzhi,LI Chang''an. Analysis of Harmonic in Non-solidly Earthed Network and Its Influences on Harmonic-based Earth Fault Protection[J]. Automation of Electric Power Systems, 2011, 35(6): 60-64
Authors:XUE Yongduan  GAO Xu  SU Yongzhi  LI Chang''an
Affiliation:XUE Yongduan1,GAO Xu2,SU Yongzhi3,LI Chang'an4(1.China University of Petroleum(East China),Dongying 257061,China,2.North China Grid Company,Beijing 100053,3.Shandong Electric Power Corporation,Jinan 250001,4.Shandong Construction Machinery Group Co.Ltd.,Qingzhou 262500,China)
Abstract:According to the principles of harmonic-based earth fault protection(identification to the line with a single phase to earth fault) in non-solidly earthed network,the characteristics of non-linear load,system power,fault point as a harmonic source and the faulty harmonic current generated by them are analyzed.Through harmonic-based protection system,the influences of multi-harmonic sources are studied as well.It is discovered that the harmonic sources of system power and non-linear load play dominant roles ...
Keywords:non-solidly earthed network   single phase to earth fault   harmonic analysis   earth fault protection   harmonic-based protection