首页 | 本学科首页   官方微博 | 高级检索  
     

电网黑启动情况下高压直流输电系统启动条件分析
引用本文:周剑,李建设,苏寅生. 电网黑启动情况下高压直流输电系统启动条件分析[J]. 电力系统自动化, 2011, 35(3): 92-96
作者姓名:周剑  李建设  苏寅生
作者单位:中国南方电网电力调度中心,广东省广州市,510620
摘    要:目前各电网的黑启动方案中,均未考虑在黑启动初期的直流启动.文中以天广直流为例,在PSCAD/EMTDC电磁暂态仿真软件中搭建了交、直流系统仿真模型,利用该模型研究了在电网黑启动初期直流的启动方式和条件.提出了采用绝对短路容量和有效惯性时间常数作为表征交流系统强度的指标.通过分析可知,当两侧交流系统都满足短路容量为单组滤...

关 键 词:黑启动  直流输电  PSCAD/EMTDC仿真  直流启动
收稿时间:2010-04-22
修稿时间:2010-12-14

Analysis on Start-up Conditions of HVDC System in Black-start
ZHOU Jian,LI Jianshe,SU Yinsheng. Analysis on Start-up Conditions of HVDC System in Black-start[J]. Automation of Electric Power Systems, 2011, 35(3): 92-96
Authors:ZHOU Jian  LI Jianshe  SU Yinsheng
Affiliation:ZHOU Jian,LI Jianshe,SU Yinsheng (CSG Dispatch and Communication Center,Guangzhou 510620,China)
Abstract:At present,the start-up of HVDC has not been considered at the initial stage of black-start in China.How to build the models of the AC system and HVDC with PSCAD/EMTDC is introduced,and then the start mode and start-up conditions of the HVDC in the initial stage of black-start are studied by the models.Two indices to measure the intensity of the AC system are proposed as the absolute short-circuit capacity and effective inertia constant.The HVDC can start-up in the monopolar constant current control startin...
Keywords:black-start   HVDC   PSCAD/EMTDC simulation   HVDC start-up
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号