首页 | 本学科首页   官方微博 | 高级检索  
     


Fan pressure-based testing,adjusting, and balancing of a ventilation system
Authors:Jussi Tamminen  Tero Ahonen  Jero Ahola  Simo Hammo
Affiliation:1.School of Energy Systems,Lappeenranta University of Technology,Lappeenranta,Finland
Abstract:Ventilation systems are responsible for the thermal comfort and air quality of indoor spaces. The adjustment of ventilation systems is a time-consuming task that may need multiple iterations. Incorrect adjustments of a ventilation system can reduce the quality of working and living conditions and degrade the energy efficiency of the ventilation. In this paper, a testing, adjusting, and balancing method for a ventilation system is presented that uses only the knowledge of the fan total flow rate and pressure. The method does not need additional instrumentation for the ventilation adjustment as the fan operating point can be estimated with the variable-speed drive. The method is noniterative, thereby saving time, and the ventilation system is adjusted to its minimum energy consumption setting without compromise in system operation. The proposed method is assessed with a laboratory test setup to verify the correct operation of the method in practice.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号