首页 | 本学科首页   官方微博 | 高级检索  
     

变电站开关操作瞬态电磁环境研究
引用本文:田世杰. 变电站开关操作瞬态电磁环境研究[J]. 吉林电力, 2011, 39(2): 20-22
作者姓名:田世杰
作者单位:华北电力大学,北京,102206
摘    要:针对变电站开关动作时产生的瞬态电磁环境改变对线路及电气设备的影响,采用通过实验室试验,电磁脉冲模拟器(EMP)模拟开关操作时的瞬态电磁环境,分析传输线及电气设备受到电磁干扰的情况,提出对变电站的电气设备的抗扰度实验应增加瞬态电场测试,以及二次电缆屏蔽层应双端接地并进一步采取相应防护措施等建议.

关 键 词:开关操作  变电所  瞬态电磁环境  抗干扰度  瞬态电场测试

Research on Transient Electromagnetic Environment of Switching Operation in Substation
TIAN Shi-jie. Research on Transient Electromagnetic Environment of Switching Operation in Substation[J]. Jilin Electric Power, 2011, 39(2): 20-22
Authors:TIAN Shi-jie
Affiliation:TIAN Shi-jie
Abstract:Transient electromagnetic environment during switching operation has been simulated by indoor EMP equipment based on transient electromagnetic environment change and its affect on lines and electric facilities.Disturbed situation of transmission line and electric facilities are analysed,and suggestions on adding immunity test and secondary cable shielding layer grounding are proposed for further protection.
Keywords:switching operation  substation  transient electromagnetic environment  immunity  transient electric field test  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号