首页 | 本学科首页   官方微博 | 高级检索  
     

多虚拟同步发电机并联系统控制参数对稳定性的影响分析
引用本文:涂春鸣,谢伟杰,肖凡,兰征. 多虚拟同步发电机并联系统控制参数对稳定性的影响分析[J]. 电力系统自动化, 2020, 44(15): 77-86
作者姓名:涂春鸣  谢伟杰  肖凡  兰征
作者单位:1.国家电能变换与控制工程技术研究中心(湖南大学),湖南省长沙市 410082;2.湖南工业大学电气与信息工程学院,湖南省株洲市 412007
基金项目:国家自然科学基金青年基金资助项目(51907057);湖南省自然科学基金资助项目(2018JJ3129)。
摘    要:虚拟同步发电机(VSG)技术作为支撑新能源消纳的新技术,其单机运行相关问题得到了广泛探讨,但目前鲜有文献从系统层面出发来综合分析多VSG并联系统的运行特性。基于此,文中通过建立多VSG并联系统全阶模型,明晰考虑系统延时下控制参数对VSG运行特性的作用规律。首先,简析VSG的运行原理及其并联方式,指出在综合建模时需考虑线路和负载参数。然后,对VSG单机模型进行延时修正,基于此建立多VSG并联系统的全阶小信号状态空间模型。接着,采用参与度分析法,甄别不同控制参数与高、低频稳定性之间的对应关系,并通过特征值轨迹分析各参数对系统高、低频稳定性的影响趋势及阈值。最后,仿真结果验证了理论分析的正确性。

关 键 词:虚拟同步发电机  多机并联运行  控制延时  高频稳定性  低频稳定性
收稿时间:2019-09-17
修稿时间:2020-04-01

Influence Analysis of Control Parameters of Parallel System with Multiple Virtual Synchronous Generators on Stability
TU Chunming,XIE Weijie,XIAO Fan,LAN Zheng. Influence Analysis of Control Parameters of Parallel System with Multiple Virtual Synchronous Generators on Stability[J]. Automation of Electric Power Systems, 2020, 44(15): 77-86
Authors:TU Chunming  XIE Weijie  XIAO Fan  LAN Zheng
Affiliation:1.National Electric Power Conversion and Control Engineering Technology Research Center (Hunan University), Changsha 410082, China;2.College of Electrical and Information Engineering, Hunan University of Technology, Zhuzhou 412007, China
Abstract:The virtual synchronous generator (VSG) technology is a new technology to support new energy consumption, whose related issues of single-machine operation have been widely discussed. However, few literatures are based on the system level to comprehensively analyze the operation characteristics of multi-VSG parallel system. Therefore, this paper establishes a full-order model of multi-VSG parallel system, which clearly considers the action law of control parameters on the operation characteristics of VSG with system delay. Firstly, the operation principle of VSG and its parallel mode are briefly described. It is pointed out that the comprehensive model should take the line and load parameters into account. Then, the delay of the single-machine model of VSG is corrected, and the full-order small-signal state-space model of the multi-VSG parallel system is established based on the modified model. On this basis, this paper uses the participation analysis method to clarify the correspondence between different control parameters and high-frequency and low-frequency stability. By analyzing the eigenvalue trajectory, the influence trend of each parameter on the high-frequency and low-frequency stability of the system and its threshold are analyzed. Finally, the theoretical analysis is verified by simulation.
Keywords:virtual synchronous generator (VSG)  multi-machine parallel operation  control delay  high-frequency stability  low-frequency stability
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号