首页 | 本学科首页   官方微博 | 高级检索  
     


Research on air-source heat pump coupled with economized vapor injection scroll compressor and ejector
Authors:Xu Shuxue  Ma Guoyuan
Affiliation:Beijing University of Technology, Beijing 100124, China
Abstract:The performance of the heat pump can be improved further when running under low temperature conditions when an ejector is used in a heat pump system coupled with economized vapor injection (EVI) scroll compressor. In this paper, the design method of the heat pump system with ejector (EVIe) is presented, and the process for designing the heat pump with ejector has been summarized. The optimal location of the vapor injection inlets is at the place where the vapor can inject into the working chambers when they just be closed. The reasonable value for the entrainment ratio u of the ejector is between 0.1 and 0.2. One prototype heat pump was designed under the condition of the evaporation temperature of −20 °C, and an experimental setup was established to test the prototype. The measured results demonstrated that the heating EER of the heat pump system with ejector could reach about 4% higher than that of the system without ejector when the heating capacity remained nearly constant.
Keywords:Heat pump  Air-source  Scroll compressor  Injection  Ejector  Design  Calculation
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号