首页 | 本学科首页   官方微博 | 高级检索  
     

电缆中间接头低值故障原因分析
引用本文:郭国伟.电缆中间接头低值故障原因分析[J].江西电力职工大学学报,2009(4):10-11.
作者姓名:郭国伟
作者单位:广东电网公司佛山顺德供电局,广东佛山528300
摘    要:100kV文东线由于热缩套下的环绕防水带绕包不足,导致热缩套防水带和电缆本体缺乏良好压接,水份侵入电缆接头保护壳内造成外护套绝缘电阻不合格.

关 键 词:电缆  接头故障  绝缘电阻

Analysis on the Cause of Cable Joints Low Malfunction
GUO Guo-wei.Analysis on the Cause of Cable Joints Low Malfunction[J].Journal of Jiangxi Electrical University For Staff,2009(4):10-11.
Authors:GUO Guo-wei
Affiliation:GUO Guo-wei (Foshan Electric Power Supply Bureau of Guangdong Province, Guangdong Foshan 528300, China)
Abstract:Because the waterproof cincture which is under pyrocondensation sheath is not enough, pyrocondensation sheath can/t press waterproof cincture and cable body well, the water immerges containment the vessel of cable joint , which causes the insulation resistance of 1 lOkV wen-dong transmission line outer restrictive coating is disqualification
Keywords:7cable  malfunction  insulation resistance