电力变压器直流电阻不平衡率超标案例
引用本文:董勇. 电力变压器直流电阻不平衡率超标案例[J]. 冶金动力, 2009, 0(2): 20-21
作者姓名:董勇
作者单位:济南钢铁股份有限公司能源动力厂,山东济南,250101
摘    要:济钢第二降压变电站2^#主变变压器检修中,在做主变压器直流电阻测试后,发现35kV侧C相直流电阻存在不平衡率超标准的现象,然后对变压器进行了解体检修,通过实例对此故障产生的原因及采取的防范措施作了论述。

关 键 词:变压器  直流电阻  不平衡率  防范措施

Case of Unbalance Rate Going Beyond Standard of Direct Current Resistance of Power Transformer
DONG Yong. Case of Unbalance Rate Going Beyond Standard of Direct Current Resistance of Power Transformer[J]. Metallurgical Power, 2009, 0(2): 20-21
Authors:DONG Yong
Affiliation:DONG Yong (Energy Sources and Power Plant, Jinan Iron & Steel Co., Ltd., Jinan, Shondong 250101, China)
Abstract:There was phenomenon of unbalance rate going beyond standard of C phase direct current resistance after testing of direct current resistance of the main transformer in maintenance of No.2 main transformer for No.2 step-down substation of Jinan Iron & Steel Co., Ltd. The transformer was disassembled and repaired. The reasons of fault and precautionary measures were discussed.
Keywords:transformer  direct current resistance  unbalance rate  precautionary measure